How to Choose an Automatic Transfer Switch for Critical Power Applications
When the mains supply fails, the seconds that follow decide whether a hospital keeps its lights on, a data centre keeps serving, or a high-rise keeps its lifts and fire systems running. An automatic transfer switch (ATS) is the device that makes that decision for you: it monitors the normal power source, and when it detects a failure it transfers the load to the standby source — a second mains feed or a generator set — without anyone having to touch a switch.
What an ATS actually does
An automatic transfer switch, also called an automatic changeover switch or ATSE, continuously watches the voltage of both power sources. If the normal source suffers a loss of voltage, undervoltage, overvoltage or phase loss, the controller commands the switch to move the load to the standby source. When the normal source recovers, the switch can return the load automatically, depending on the working mode selected.
Dacheng's automatic transfer switches offer three stable working positions: normal source closed, standby source closed, and both sources open (I – 0 – II). The middle "0" position matters more than it looks: in an emergency, the switch can be forced to zero, cutting off both sources at once, which is exactly what fire protection linkage requires.
Three working modes to choose from
Not every site wants the same behaviour after a transfer, so our switches offer three modes:
- Auto-transfer, auto-restore: the load returns to the normal source as soon as it recovers, whatever the state of the standby source. This is the standard choice for most commercial buildings.
- Auto-transfer, no auto-restore: the load stays on the standby source after the normal source recovers, and only returns when the standby source fails or an operator resets it. This avoids repeated switching when the mains supply is unstable.
- Mutual standby: either source can serve as the working source, and the switch only changes over when the source in use fails. This suits installations where two feeds are genuinely equal.
Transfer and return delays are adjustable — typically 0, 5, 15 or 30 seconds — so a brief voltage dip does not trigger an unnecessary changeover, and a generator has time to reach stable voltage before taking the load.
PC class or CB class?
Automatic transfer switches fall into two classes under IEC 60947-6-1. PC class switches, such as our QGLD series, are load-break switches: they make and break the load current but rely on an upstream protective device for short-circuit protection. CB class switches, such as our QATSN series, use circuit breakers as the switching elements and provide short-circuit and overload protection themselves. The CB class is the right answer where the transfer switch is also expected to protect the circuit; the PC class is the economical choice where protection already exists upstream.
Ratings that matter when you specify
A transfer switch is specified by its frame, not by a single number. Dacheng's QGLD series covers rated currents from 16 A up to 3,200 A at 380 V AC, 50 Hz, in 3-pole and 4-pole versions, with a rated insulation voltage up to 1,000 V and a rated impulse withstand voltage of 6 to 12 kV depending on frame size. The QATSG series covers 32 A to 800 A with a rated insulation voltage of 750 V and an impulse withstand voltage of 8 kV. Transfer time is typically 0.5 to 1.2 seconds depending on frame size, and mechanical endurance reaches 10,000 operations.
Equally important is what the controller watches: undervoltage, overvoltage and phase loss on both sources, with self-diagnosis and fault alarms. Optional functions include fire alarm linkage, automatic generator start control, programmable signal output relays and RS-485 communication, so the switch can report its position to a building management system.
Where ATS belongs
Automatic transfer switches are specified wherever an interruption is not acceptable: fire protection systems, hospitals and operating theatres, banks and data centres, high-rise buildings, airports, shopping centres, and continuous industrial production lines. They are also used for straightforward mains-to-generator switching in commercial and industrial installations.
When you select a switch, check five things: the rated current against your real load, 3-pole or 4-pole (a 4-pole switch is needed where the neutral must be switched), the transfer mode your operation requires, whether you need mains-to-mains or mains-to-generator control, and the environment — our switches are rated for -5 °C to +40 °C and altitudes up to 2,000 m. Finally, plan a test: operate the switch through a full transfer at least once every three months, using the test button or a manual changeover, so you know it will work on the day it is needed.